134
WDA
WDA
039 045 050 060 070 080 090 110 120 130
38,8 44,3 52,4 59,3 66,0 78,9 90,4 99,7 112,8 125,8
13,2 15,3 19,4 21,1 22,4 25,9 29,6 33,4 37,7 42,2
6,7 7,6 9,0 10,2 11,3 13,5 15,5 17,1 19,4 21,6
111 132 140 162 171 208 259 265 312 320,5
32 42 44 53 62 68 74 80 88,5 97
400/3/50
2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
74 74 75 76 76 77 77 78 78 79
46 46 47 48 48 49 49 50 50 51
152 162 190 210 240 260 300 320
145,0 162,6 178,3 197,8 221,4 245,8 277,5 314,0
48,0 53,9 59,2 66,5 76,3 85,1 96,9 108,6
24,9 27,9 30,6 33,9 38,0 42,2 47,6 53,9
358,5 375,4 333 345 400,5 417,5 472,4 506,2
113,9 130,8 148, 160 177 194 227,8 261,6
400/3/50
2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2
79 79 80 82 82 82 84 84
51 51 52 54 54 54 56 56
Versions WDA/EV
Cooling capacity
(5)
kW
Compressor input power
(5)
kW
Water flow
(5)
m
3
/h
Peak current A
Max input current A
Power supply
V/Ph/Hz
Compressors / Circuits n°
Sound power level
(3)
dB(A)
Sound pressure level
(4)
dB(A)
Versions WDA/EV
Cooling capacity
(5)
kW
Compressor input power
(5)
kW
Water flow
(5)
m
3
/h
Peak current A
Max input current A
Power supply
V/Ph/Hz
Compressors / Circuits n°
Sound power level
(3)
dB(A)
Sound pressure level
(4)
dB(A)
(5)
For EV version: condensing temperature 50 °C, water temperature in/out 12/7 °C.
(3)
Sound power level in accordance with ISO 9614. (LS verions).
(4)
Sound pressure level at 10 mt from the unit in free field conditions direction factor Q = 2 in accordance with ISO 9614 (LS versions)
and control and pressure safety device (for
compliance with PED regulations).
Also available is an electronic expansion
valve with electronic control which optimi-
ses the efficiency in part load conditions
(option),
COMPRESSORS
The compressors utilised are scroll type.
All compressors are fitted with a crankcase
heater and each compressor has a klixon
embedded in the motor winding for thermal
overload protection. The crankcase heater
is always energised when the compressor
is in stand-by. Access to the compressors
is through the front and side panels. The
compressors used are all in tandem con-
figuration. This results in much higher ef-
ficiencies at part loads compared to units
with independent refrigerant circuits.
CONDENSERS
The condensers are braze welded, plate
type heat exchangers, manufactured from
FRAME
All WDA units are made from hot-galvani-
sed sheet steel, painted with polyurethane
powder enamel and stoved at 180°C to
provide maximum protection against cor-
rosion. The frame is self-supporting with
removable panels. All screws and rivets
used are made from stainless steel. The
standard colour of the units is RAL 9018.
REFRIGERANT CIRCUIT
The refrigerant utilised is R410A. The refri-
gerant circuit is assembled using internatio-
nally recognised brand name components
with all brazing and welding being perfor-
med in accordance with ISO 97/23. Each
refrigerant circuit is totally independent
from the other. Failure of one circuit does
not influence the other circuit. The refrige-
rant circuit includes: sight glass, filter drier,
reversing valve (for heat pump version
only), one way valve (for heat pump version
only), liquid receiver (for heat pump version
only), Schraeder valves for maintenance
AISI 316 stainless steel. Utilisation of this
type of exchanger results in a massive re-
duction of the refrigerant charge of the unit
compared to the traditional shell-in-tube
type. A further advantage is a reduction in
the overall dimensions of the unit and an in-
crease in efficiency of the refrigerant cycle
in partial loads.. From size 039 to size 162
they have a single water side circuit, from
size 144 upwards they are double circuit
“cross flow” type.
EVAPORATORS
The evaporators are braze welded, plate
type heat exchangers, manufactured from
AISI 316 stainless steel. From size 039 to
size 162 they have a single water side cir-
cuit, from size 190 upwards they are double
circuit “cross flow” type.
All units are supplied with a sub-cooler to
enhance the performance of the refrigerant
cycle. The evaporators are factory insula-
ted with flexible close cell material and are
supplied with a temperature sensor as anti-
freeze protection.